Back to products
Information

The T2100 measures the current through an external 5A CT attached on phase L1. The phase angle (phi) is determined from the voltage measurement across L1 and L2. The T2100 calculates the reactive current as I x sin phi. If the reactive current becomes negative and exceeds the preset level (0.5 – 1.4 x I), the pick-up LED will ignite and the trip delay timer (3 – 30 seconds) will activate. The built-in trip relay will energize after the delay has passed, provided that the preset trip level was continuously exceeded during the time of the delay.

Related products: