The SELCO T3500 Frequency Deviation Relay will, based on a simple AC voltage measurement, monitor the change in frequency over a time period of one second.
The T3500 Pick up LED will ignite as soon as the voltage frequency has changed more than 0.5 Hz to 1.5 Hz per second, while the internal relay (and the relay indication LED) activates after the frequency deviation has existed for more than 100 milliseconds.
The 100 millisecond delay can be omitted by bridging two external connection terminals. An alternative delay of 50 milliseconds can be obtained by inserting a resistor between the two terminals. The Pick Up and Relay LED will ignite simultaneously if the delay is omitted.
Related products:
T2000 Reverse Power Relay
T2100 Excitation Loss Relay
T2200 Overcurrent Relay
T2300 Short Circuit Relay
T2400 Dual Overcurrent Relay
T2500 Overcurrent and Short Circuit Relay
T2600 Dual Current Relay
T2700 Overload Relay
T2800 Overcurrent or Earth Fault Relay
T2900 Differential Current Relay
T3000 Frequency Relay
T3100 Voltage Relay
T3200 Insulation Monitoring Relay
T3300 Voltage Relay 3 phase
T8400 Blackout Limiter
Product
Catalogue
Data sheet
SELCO
- P.O. Box 113 - Betonvej 10 - DK-4000 Roskilde - Phone: +45 70 26 11 22 - Fax: +45 70 26 25 22 Copyright © 1995 - 2009 -
SELCO